TL;DR
Recent developments include Vantage reserving more than a gigawatt of factory capacity for Heron Power solid-state transformers and a NiSource-Microsoft power agreement that includes a 600-megawatt battery. They reflect a wider push toward 800-volt direct-current systems and storage, but projected efficiency gains are largely vendor claims and deployment details remain limited.
Vantage reserved more than a gigawatt of factory capacity for Heron Power solid-state transformers designed to convert grid electricity directly into 800-volt direct current, while a separate NiSource-Microsoft agreement includes a 600-megawatt battery. The deals put batteries and high-voltage DC distribution in the spotlight as AI data centers seek to supply increasingly power-hungry racks, amid growing power constraints; they do not, by themselves, confirm widespread deployment or independently measured efficiency gains.
Vantage made its reservation on October 21, according to the source report. The product is intended to bring grid power onto an 800-volt DC system, reducing the number of conversion stages between incoming electricity and computing equipment. Heron’s transformer also incorporates storage, which could help buffer changing demand. The report does not say how many units Vantage will receive, when they will be installed, or how much of its data center capacity they will serve.
On October 16, NiSource signed a 20-year power agreement with Microsoft that the report says adds about 1,100 megawatts of generation and a 600-megawatt battery. The agreement is a separate development from Vantage’s equipment reservation; it does not establish that the battery will connect to an 800-volt DC system. The source provides no project-level schedule or detail on how the battery will be operated.
The technical case for DC is tied to rising rack demand. The International Energy Agency says AI-server power density increased 11-fold from 2020 to 2025 and is projected to quadruple again by 2027. NVIDIA’s reference design proposes converting 13.8-kilovolt grid power to 800-volt DC near the facility perimeter, then distributing it to racks. NVIDIA says its approach could use 45% less copper than 415-volt AC distribution and improve end-to-end efficiency by up to 5% compared with current 54-volt systems. Those figures are company claims, not independent measurements; the source says full-scale production is planned with Kyber systems in 2027.
Infographic 01 · From grid to rack
AI racks near a megawatt are outgrowing the AC power chain.
Why the industry is moving to 800-volt direct current: fewer conversions, less copper, batteries on the main path. The numbers are vendor figures with different baselines, so they cannot be added up.
Today: many conversions
Typical AC chain from the grid to the rack
- Medium-voltage AC from the grid
- Transformer steps it down to low-voltage AC
- UPS converts to DC for the batteries and back to AC
- Distribution units feed the racks
- Every server power supply converts AC to DC again
Each stage loses energy, and almost all of the loss becomes heat the cooling system must remove.
800 V DC: convert once, outside
NVIDIA reference design, full-scale production planned with Kyber racks in 2027
- 13.8 kV AC from the grid
- Converted once to 800 V DC at the edge of the site, batteries on the same DC bus
- 800 V DC busway to the racks
- Stepped down inside the rack, for 1 MW racks and beyond
Bridge for existing halls: a “sidecar” cabinet next to the rack converts AC to 800 V DC, while the old chain stays in place.
Power lost per MW delivered to the rack
kW, SMA white-paper model vendor model
What NVIDIA says 800 V DC changes
NVIDIA’s engineering claims claim
Sources: NVIDIA technical blog (20 May 2025, updated 31 Jul 2025); SMA America, sponsored content in Utility Dive (26 Oct 2026). Rack density: IEA, Key Questions on Energy and AI (Apr 2026) (AI server power density 11× from 2020 to 2025, a further 4× by 2027).
Powered by Thorsten Meyer AI
How DC Changes Data Center Power
Moving conversion closer to the building’s electrical connection could reduce the amount of equipment and wiring needed to deliver power to high-demand racks. In a traditional design, incoming AC is stepped down and converted through several stages before servers use low-voltage DC. Each conversion loses some energy as heat. At rack demands approaching a megawatt, the weight and space required for low-voltage conductors also become a constraint, according to NVIDIA’s engineering discussion.
Batteries can address a different problem: the speed and variability of AI workloads. Storage connected to the power system may absorb short-lived demand swings, provide backup during disturbances, or help a facility manage how quickly it increases its load. The IEA estimates that data centers could have 20–25 gigawatts of battery capacity by 2030, while saying their potential role as grid assets depends on incentives. That is a projection, not a tally of installed capacity.
The implications reach beyond operators. The IEA projects global data center electricity use will rise from 485 terawatt-hours in 2025 to 950 terawatt-hours in 2030. More demand can increase pressure on generation and transmission, but these developments alone do not show that household bills will rise by a particular amount. The effect depends on where projects are built, how new infrastructure is funded, and how utilities allocate costs.
Products Worth Considering

LG UltraGear 27-Inch QHD OLED Gaming Monitor, 240Hz, 0.03ms, G-SYNC Compatible, FreeSync Premium Pro, HDMI 2.1

LG UltraGear 32GX850A-B 32-Inch 4K UHD Glossy OLED Gaming Monitor

LG UltraGear 45GX900A-B 45-Inch Curved OLED Gaming Monitor
As an affiliate, we earn on qualifying purchases.
From AC Conversion to 800 Volts
Most data centers have traditionally received alternating-current power, transformed it to lower voltages, and converted it to DC for servers. The multiple conversion stages and resulting heat become harder to manage as rack loads climb. NVIDIA says a one-megawatt rack supplied at 54 volts could require up to 200 kilograms of copper busbar and substantial space for power equipment. That is the company’s estimate for its design comparison, not a universal measurement across facilities.
An 800-volt architecture is one proposed response: convert incoming medium-voltage AC once near the facility edge, then distribute DC toward the racks. Operators may not need to replace every existing system at once. Utility Dive’s October 26 article, which the source identifies as sponsored content by inverter maker SMA America, describes “sidecars”: conversion cabinets beside racks that could allow 800-volt equipment to operate in halls built around AC infrastructure. SMA’s modeled comparison estimates about 80 kilowatts of losses when delivering one megawatt through a traditional chain, versus about 20 kilowatts in its 800-volt DC scenario. These are vendor-model results, not independently verified operating data.
Electricity supply and equipment availability are also constraints. The IEA says transformers can take two to three years to arrive and grid connections can take five to ten years in many places. Berkeley Lab reported about 2,300 gigawatts of projects in the U.S. interconnection queue at the end of 2024; only 13% of earlier requests were ultimately built. Queue capacity is not the same as completed or committed generation.
“The company says 800-volt DC could require 45% less copper than 415-volt AC distribution.”
— NVIDIA
Deployment and Cost Questions Remain
The reported announcements leave open how quickly the systems will reach operating sites. The source does not provide Vantage’s delivery schedule, the number or location of Heron transformers involved, or whether the reserved capacity will translate into completed equipment orders. It also gives no details on the NiSource-Microsoft battery’s location, charging arrangements, or role in managing data center demand.
Performance remains unverified at operating scale. The copper and efficiency figures cited for 800-volt DC come from NVIDIA and SMA, while SMA’s comparison is a modeled scenario in sponsored material. Actual results may vary with facility design, workload, cooling, and how much legacy equipment remains. The source does not provide independent field measurements comparing the new systems with existing data center power chains.
It is also unclear how much battery storage will be installed specifically at data centers, how often it will serve the grid, or who will pay for the supporting power infrastructure. The source cites average U.S. residential electricity prices of 18.21 cents per kilowatt-hour in 2026, compared with 17.30 cents in 2025, and a 41% rise in wholesale prices in the PJM region. Those figures do not establish that data center demand caused the changes or that the same effect applies nationwide.
Orders, Pilots and Grid Timelines
Near-term evidence will come from equipment deliveries, facility deployments, and operating measurements. The source says NVIDIA plans full-scale production of its 800-volt approach with Kyber systems in 2027. Vantage’s factory-capacity reservation may support future supply, but the report gives no installation date. Details on the NiSource-Microsoft generation and battery projects will be needed to establish their construction and operating timelines.
Operators and utilities will also need to show how DC distribution and storage work alongside existing AC halls and grid connections. Independent measurements of conversion losses, copper use, reliability, and battery performance would help test vendor projections. Meanwhile, lengthy transformer and interconnection lead times mean that power delivery—not only chip availability—may continue to shape when new AI data center capacity can come online.
Key Questions
What does 800-volt DC mean for an AI data center?
It describes distributing direct current at 800 volts closer to data center racks, after converting incoming grid power near the facility. The proposed design aims to reduce conversion stages and the amount of copper needed compared with lower-voltage distribution.
Why are batteries being added to data center power plans?
AI workloads can cause demand to change quickly. Batteries may help buffer those swings, support a site during grid disturbances, or manage how quickly it ramps up. The projects and operating plans vary, and the source does not establish that every data center battery will perform all these roles.
Are the claimed efficiency gains independently confirmed?
No independent measurements are provided in the source. NVIDIA’s copper and efficiency figures are vendor claims, and SMA’s comparison comes from a model in sponsored Utility Dive content.
Does the NiSource-Microsoft agreement use 800-volt DC?
The source reports a 20-year power agreement that adds about 1,100 megawatts of generation and a 600-megawatt battery. It does not say that the battery or generation will connect to an 800-volt DC data center system.
Will these projects raise household electricity bills?
The source does not establish a direct effect on household bills. Costs depend on project locations, electricity supply, grid upgrades, and how utilities allocate expenses. Higher data center demand is not, by itself, proof of a specific change to residential rates.